• HEPA vs. ULPA Filters: A Data-Driven Comparison Based on EN 1822 Standards

      Confused about the difference between HEPA and ULPA filters? This data-driven comparison breaks down EN 1822 efficiency classes, explains MPPS testing methodology, and helps you choose the right filter based on your cleanroom requirements and application needs.

      HEPA vs. ULPA Filters

      A Data-Driven Comparison Based on EN 1822 Standards

      The core difference between HEPA and ULPA filters lies in their filtration efficiency and the cleanroom requirements of their application scenarios. HEPA (High Efficiency Particulate Air) and ULPA (Ultra Low Penetration Air) filters are classified according to the European standard EN 1822, which uses particle counting methods to determine filtration efficiency based on MPPS (Most Penetrating Particle Size) —the particle size that is most difficult for a filter to capture. For glass fiber filter media, the MPPS typically falls in the range of 0.12μm to 0.25μm. Efficiency measured at this particle size most accurately reflects the true performance of the filter.

      1. EN 1822 Standards: Data-Based Efficiency Classification

      According to EN 1822-1:2009, filters are divided into three groups: E-group (EPA, sub-efficient), H-group (HEPA, high-efficiency), and U-group (ULPA, ultra-low penetration). The detailed parameters for H13, H14, and U15 are as follows:

      Category Grade Overall Filtration Efficiency (at MPPS) Penetration Rate (Integral Value) Typical Achievable Cleanliness Level
      HEPA H13 ≥ 99.95% ≤ 0.05% ISO 7-8 (Class 10,000–100,000)
      HEPA H14 ≥ 99.995% ≤ 0.005% ISO 5-6 (Class 100–1,000)
      ULPA U15 ≥ 99.9995% ≤ 0.0005% ISO 3-4 (Class 1–10)

      Key data insight: H14 allows only 1/10 of the penetration rate of H13 (0.005% vs. 0.05%), and U15 allows only 1/10 of the penetration rate of H14 (0.0005% vs. 0.005%). This reflects the industry adage: “Each additional ‘9’ in efficiency multiplies the cost by an order of magnitude.”

      2. Filter Media and Filtration Mechanisms

      Both HEPA and ULPA filter media are primarily made of glass fiber through a wet-laid process, resulting in uniform fiber distribution, high dust-holding capacity, and low resistance. The fiber diameter can be controlled at the micron level, forming a three-dimensional network of microporous structures.

      Beyond the sieving effect, Brownian diffusion plays a significant role in capturing nanoscale particles. HEPA filters achieve a filtration efficiency of ≥ 99.97% for 0.3μm particles, while ULPA filters can reach ≥ 99.999% for 0.1–0.2μm particles and ≥ 99.9999% for 0.3μm particles.

      3. Pressure Drop and Energy Consumption: The Other Side of the Data

      The higher efficiency of ULPA filters does not come without cost. The following is a set of measured data: under identical size (610×610×292mm) and airflow (1,000 CMH) conditions, the initial pressure drop of an H14 HEPA filter is approximately 220 Pa, while that of a U15 ULPA filter is approximately 280 Pa—approximately 27% higher.

      H14 HEPA
      220 Pa
      Initial pressure drop @ 1,000 CMH
      U15 ULPA
      280 Pa
      Initial pressure drop @ 1,000 CMH · 27% higher

      For every 60 Pa increase in pressure drop, fan power needs to increase by approximately 10–15%. This translates to an extra 200–400 kWh of annual energy consumption per FFU (Fan Filter Unit). For a semiconductor fab with 1,000 FFUs, electricity costs alone could rise by hundreds of thousands of yuan annually.

      4. Cleanliness Levels and Typical Applications

      The filter grade directly determines the achievable cleanroom classification. According to ISO 14644-1:

      Filter Grade Achievable ISO Cleanliness Level Typical Application Scenarios
      H13 ISO 7-8 Hospital operating rooms, ICUs, pharmaceutical manufacturing, nuclear power plant exhaust systems, high-end air purifiers
      H14 ISO 5-6 Semiconductor manufacturing, sterile filling, biological safety cabinets
      U15 ISO 3-4 Chip fabrication lithography areas, nanotechnology research, Class 100/10/1 cleanrooms

      For example, in biological safety cabinets: HEPA filters typically achieve ISO Class 5 (Class 100) cleanliness, while ULPA filters can achieve ISO Class 3 (Class 1) —two grades higher.

      5. Selection Strategy: Balancing Precision, Energy, and Cost

      ULPA is not always the better choice. Keep these three key points in mind when selecting:

      • Do not blindly pursue the highest grade: Over-specification increases both procurement costs and long-term operational expenses. Always confirm the required ISO Class first, then select the appropriate filter grade.
      • Pay attention to pressure drop and energy consumption: Verify that the filter’s pressure drop matches the existing fan curve to avoid fan overload or excessive energy consumption.
      • Set a reasonable replacement schedule: A common practice is to set the final pressure drop at 2–2.5 times the initial pressure drop as the replacement trigger. For an H14 HEPA with an initial pressure drop of 220 Pa, the final pressure drop should be set at 440–550 Pa.